Pats & Accessories
29
EasyPAT Manual PAT Tester - professionalEPAT2100
INSULATION TEST
Same as EasyPAT 1600
(see opposite)
EARTH CONTINUITY (8A & 25A)
Same as EasyPAT 1600
(see opposite)
EARTH CONTINUITY (100mA)
Same as EasyPAT 1600
(see opposite)
RUN CURRENT TEST
Range: 0-19.9A
Usable Range: 0 - 13.0A
Accuracy: ±10% of reading ±1 digit
EARTH LEAKAGE TEST
Range: 0 - 19.9mA
Accuracy: ±10% of reading ±1 digit
FLASH TEST
Test Voltage: 1.5kV AC - Class I.
3.0kV AC - Class II
Display Range: 0-19.9mA AC
Usable Range: 0-3mA AC (current
trip @ 4mA nominal)
Accuracy: ±5% of reading ±1 digit
LEADS
Earth Continuity: 1.5 metre long,
detachable lead with a heavy duty,
shrouded crocodile clip.
Flash Gun: A safety gun, giving extra
user protection for flash testing.
110/ 240V Adaptor:
110V 16A plug (BS 4343) to
240V 13A free socket (BS 1363)
230V IEC Adaptor: 13A BS 1363
plug to IEC320 connector, 230mm
long.
SOCKETS
Mains: 240V 13A to BS 1363.
110V 16A to BS 4343
Flash: 4mm high voltage safety socket
Lead test: IEC 320
LAMPS
Flash: Neon lamp which illuminates
when flash test is active.
Over Temperature: Red LED which
illuminates when the temperature
limit of the instrument is exceeded.
Lamp 1/ Lamp 2: Red LED’s which
illuminate to indicate lead ‘polarity’
for extension lead test facility.
SUPPLY
Voltage: 110V/240V ±10% 50/60Hz
Power Consumption: 10/220V A
(excl run)
Complies with
EMC: Meets BS EN 50081-1
BS EN 50082-1
LVD: Meets BS EN 61010-1
Dimensions: 330 x 263 x 144mm
Weight: 4.6kg approx
Includes: manual, removable earth
bond lead (TL66), flash probe
(TL166) and 110V adaptor (TL150).
Adaptor to test 230V plug to socket
leads (EX332). All contained in
attached carry bag.
A high speed, fully specified dual voltage PAT tester which is ideal for contractors and
workshops. Simple push button test selection maximises productivity.
With an excellent test result display, the EasyPAT 2100 is the best choice in manual
testers. The flash test is particularly useful if any repairs are carried out.
See pages 32 & 33 for accessories and page 30 for labels
MAREPAT2100 easyPAT 2100 manual PAT tester £748.50
TC2C calibration £55.00
MAREX331 optional adaptor to test 110V plug to 110V socket leads £12.95
• Does ALL 5 tests
• Tests at either 110V or 230V,
dependant on supply voltage
• No need for computer links
• 25A, 8A and 100mA (for
computers, etc) earth bond tests
selectable with a simple rocker
switch
• Now supplied complete with a
built in extension lead tester
• Tests 110V appliances from 110V
supplies and 240V appliances
from 240V supplies.
“Pressing one button
per test
speeds it up”
N