1000A AC Clamp Meter
Multimeters & Clamp Meters
CM56
Display: 3½ digit LCD bargraph
AC V: 1mV to 750V, autoranging
(50Hz to 300Hz) (4 ranges)
Accuracy: ± (1.5% rdg + 4 dgts)
AC A: 10mA to 1000A (3 ranges)
(50Hz to 400Hz)
DC V: 100μV to 1000V (5 ranges)
Accuracy: ± (0.5% rdg + 1 dgt)
Resistance Ranges: 320Ω, 3.2kΩ,
32kΩ, 320kΩ, 3.2MΩ, 30MΩ
Resolution: 0.1Ω on 320Ω range
Accuracy range:
± (1.0% rdg + 3 dgts) 320Ω to 320kΩ
± (1.5% rdg + 3 dgts) on 3.2MΩ
± (2.5% rdg + 5 dgts) on 30MΩ
Ohms: 100mΩ to 30MΩ (6 ranges)
Continuity: Buzz at <20Ω
Diode test
Frequency: 0.1Hz - 32kHz (3 ranges)
Max conductor: 57mm Ø or 70 x
18mm bus bar
Auto Power Off: After 10 minutes
Dimensions: 277 x 102 x 49mm
Weight: 540g approx
Includes: leads (TL16), case, battery
& manual
This has a large display combining a clear 3½ digit
readout with a responsive 34 segment bargraph,
useful for representing varying signals.
For general purpose use it is autoranging on AC and
DC voltage, with resistance to 30MΩ and a beeper for
the low resistance continuity range.
The CM56 also measures frequency with 0.1Hz
resolution, allowing accurate determination of mains or
generator frequencies. Reading Hold and AC Peak
functions complete the impressive capability of this
clamp.
26
True RMS 1000A AC/DC Clamp Meter CM58
Display: 3½ digit LCD bargraph
AC V: 100μV to 750V, autoranging
(50Hz to 500Hz) (5 ranges)
Accuracy: ± (1.5% rdg + 4 dgts)
AC A: 100mA to 1000A (2 ranges)
(true RMS, 50Hz to 400Hz)
Accuracy: 0-600A ± (1.5% rdg +5
dgts), >600A ± (2% rdg + 5 dgts)
DC V: 100μV to 1000V, autoranging
(5 ranges)
Accuracy: ± (0.5% rdg + 1 dgt)
DC A: 100mA to 1000A (2 ranges)
Accuracy: 0-600A ± (1.5% rdg + 5
dgts), 600-800A ± (2.5% rdg + 5 dgts)
>800A ± (3.5% rdg + 5 dgts)
Ohms: 100mΩ to 40MΩ (6 ranges)
Capacitance: 1pF to 40μF,
autoranging (5 ranges)
Frequency: 0.1Hz to 400kHz,
autoranging (5 ranges)
Continuity: Buzz at <40Ω
Max conductor: 57mm Ø or 70 x
18mm bus bar
Diode test
Dimensions: 277 x 102 x 49mm
Weight: 540g approx
Includes: leads (TL16), case,
battery & manual
This meter is the top model in this
outstanding range of clamps with
true RMS AC voltage and current
measurement.
It measures AC and DC current
to 1000A, has voltage, resistance,
frequency and capacitance functions
and is autoranging (except voltage).
The bargraph has 42 segments for
better resolution of changing
readings. The CM58 has Max and
Min reading memories, AC Peak
and Hold features and Diode test.
Manual range change/hold is
provided for optional override of
the autoranging functions.
MARCM56 1000A AC clamp meter £108.00
TC2A calibration £27.00
MARTL55 optional fused test leads £32.40
MARTC68 carry case £12.95
MARCM58 true RMS 1000A AC/DC clamp meter £168.00
TC2B calibration £39.00
MARTL55 optional fused test leads £32.40
MARTC68 carry case £12.95
N
N
Comentários a estes Manuais